Isolate the switch
in GN
- 1.5 / S200-1.6 family |
| 1.The use of the products
and scope of application:
GN -
1.5 / S200-1.6 family isolate switch (hereafter
referred to as switch) suitable for and exchange
50/60 Hz mainly, specified voltage 1140 Vs,
the supreme voltage is 1500V, the specified
electric current is a device in one of 200
As. Except that the ones that make and isolate
power are used, also can used in frequent
putting through and assign to and break the
circuit.
2.Technological characteristic of
the switch:
2.1 switch for person who
open, main circuit it counts to be three very
much, operation mode as manual very much,
the switch attaches three fuse box seat and
enclosure as the switch of a small-scale relay
connected with the body very much. The design
of this switch has fully absorbed domestic
and international advanced technology, and
actual conditions and technological level
of combining our country have made very good
result, have the characteristics that the
project organization rational, aesthetic in
appearance, works is reliable .
3.Main performance index of the switch:
3.1 switches of
basic parameters meet form 1 |
| A basic parameter of form
| Serial number |
Name
|
Unit
|
Parameter |
Remarks |
| 1
|
Specified voltage |
V
|
1140
|
|
| 2
|
Specified electric current |
A
|
200
|
|
| 3
|
Specified frequency |
Hz
|
50/60
|
|
| 4
|
Isolate the fracture and make the
distance |
mm
|
>=
22 |
|
| 5
|
Alternate centre-to-centre spacing
|
mm
|
85.5
± 0.175 |
|
| 6
|
Touch
the head pressure |
N
|
>=
100 |
|
| 7
|
Shut,
assign to the strength of operating
|
N
|
200
<= F <= 600 |
Adopt
the long handle of 210mm |
|
| See form 2s in 3.2 amount
put through disconnected ability |
2 amount put through disconnected ability
forms of form
| Experimental electric current virtual
value (A) |
Experimental voltage (V) |
Power
factor (COS ر0.05) |
| 3Ie
|
1.05Ue
|
0.65
|
|
3.3 amount electric current
2.4KA in short-term, duration 1 S, specified
peak value tolerance electric current 6 KAs.
3.4 worker able to bear and
see voltage 3 form frequently, one minute such
as test period. |
3
workers of form are able to bear the voltage
of receiving frequently
| Classification
|
Position
that exert pressure |
The worker
is able to bear the voltage of receiving
frequently in one minute (virtual
value) |
| Main circuit
|
Phase --Phase
Phase --Ground |
4200V |
| Main circuit
|
Isolate among
the fractures |
4200V |
| Auxiliary
circuit |
Electrification
position place correctly |
2000V |
|
|
3.5 thunder and lightnings assault the voltage
of tolerance and see form 4s |
| Form
4 thunder and lightnings assault the voltage
of tolerance
| Classification
|
Position
that exert pressure |
The thunder
and lightning assault the voltage
(peak value ) |
| Main circuit
|
Phase --Phase
Phase --Ground |
20KV |
| Main circuit
|
Isolate
among the fractures |
23KV |
|
The measurement value of
resistance of main return circuit of 3.6 switches
is not greater than 100 ¦Ì¦¸.
3.7 switches of Machankal Durability is 10000 times. |
| 4.The products carry out the standard
|
 |
| 5.Size of appearance and installation
measurement |
| External
dimension 5 of form and size of installation
Unit: mm
| Classification
|
The size
of appearance (long x is high x is
wide) |
Install
the size (four Kong Ø 8.5)
|
| Noumenonn
of the switch |
319±2x150±1.25x388±1.8 |
210±0.575x219±0.575 |
| Fuse box
seat |
257±6x53.5±0.95x120±1.1 |
162±0.5x100±0.435 |
|
| 6.Products sketch |
 |
7.The products carry
out the standard
GB/T14048.1-2000 hypobaric switchgear and controlling
the general provisions of equipment;
GB14048.3-93 hypobaric switch control equipment
hypobaric switch isolator isolate the switch
and fuse box make the electric apparatus up;
.
GB/T11022-1999 high-pressure switchgear interchangeable
technological condition ;
The machinery under GB/T3309-1989 high-pressure
switchgear normal atmospheric temperature is
tested. |